Thermostatic Expansion Valve (TEV) and Superheat:
- Function: TEV maintains normal evaporator superheat under small load variations by adjusting refrigerant flow.
- Limitations:
- Low Load Conditions: TEV struggles to maintain superheat under low airflow conditions (e.g., dirty filter, evaporator, or blower wheel), leading to lower than normal superheat.
- High Load Conditions: During high load scenarios (e.g., turning on the AC in a hot, humid space), the TEV may result in higher than normal superheat.
- Low Refrigerant Charge: If the system is undercharged, TEV cannot maintain proper superheat as there isn't enough refrigerant to meet demand.
Measuring Superheat:
Evaporator Superheat:
- Measured by taking the suction line temperature at the evaporator outlet, near the TEV bulb, and subtracting the evaporating temperature from it.
- This measurement is crucial for assessing the efficiency of the evaporator coil.
Total Superheat:
- Measured 6 inches from the compressor on the suction line or near the service port on an air conditioning condensing unit.
- Total superheat considers the entire suction line and is important for evaluating the system's overall refrigerant charge and protecting the compressor.
Manufacturer Specifications:
- Heatcraft (Evaporator Coil Manufacturer):
- Recommends 10°F of evaporator superheat, focusing on evaporator efficiency.
- Emerson (Compressor Manufacturer):
- Recommends 20°F of total superheat, focusing on preventing floodback to protect the compressor.
Air Conditioning Manufacturers:
- Often specify total superheat as an indicator of proper refrigerant charge.
- Line Set Considerations:
- Factory charge is typically sufficient for 15 to 25 feet of line set between indoor and outdoor units.
- Adjust refrigerant charge based on the actual length of the line set:
- Longer Line Set: Add more refrigerant.
- Shorter Line Set: Remove some refrigerant.
- Use a charging chart in conjunction with total superheat measurements for precise adjustments.
Key Points to Remember:
- Understand the distinction between evaporator superheat and total superheat.
- Follow manufacturer guidelines for superheat to ensure optimal system performance and compressor protection.
- Regularly check and maintain proper airflow to avoid issues with superheat control.