Examples of Run Capacitors
- Older Style: Single run capacitors with two terminals, often contained PCBs (polychlorinated biphenyls), which were banned in 1979.
- Newer Style: Typically metal and oil-filled, no PCBs, may have three terminals, not polarized, and internally protected.
Run Capacitors in Circuits
- Permanent Split Capacitor (PSC) Motor:
- Common in split-phase motor arrangements.
- Run capacitor in series with start winding.
- No starting relay or start capacitor.
- Balanced refrigerant pressures required for starting.
- Capacitor Start-Capacitor Run Motor:
- Includes start capacitor and starting relay (e.g., potential relay).
- Run capacitor remains in the circuit after the start capacitor is removed.
Function and Benefits
- Phase Shift: Provides a phase shift to start winding for better running efficiency.
- Current Limitation: Limits current to the start winding.
- Running Efficiency: Reduces motor current by up to 20%, improving efficiency.
- Starting Torque: Provides some starting torque, though mainly enhances running efficiency.
Differences Between Start and Run Capacitors
- Color:
- Start capacitors: Black.
- Run capacitors: Gray.
- Enclosure and Dielectric:
- Start capacitors: Plastic enclosure, dry dielectric, designed for short-duration use.
- Run capacitors: Metal enclosure, oil-filled dielectric, designed to dissipate heat and remain in the circuit.
- Microfarad Ratings:
- Start capacitors: Higher microfarad values, often a range (e.g., 238-262 µF).
- Run capacitors: Single microfarad value (e.g., 45 µF).
Dual Run Capacitors
- Purpose: Saves space by combining two capacitors into one.
- Configuration:
- Three terminals: Common, Fan, Herm (for hermetic compressor).
- Common terminal for line voltage feed.
- Fan terminal for condenser fan motor start winding.
- Herm terminal for compressor start winding.
- Replacement: Replace the entire unit if one capacitor fails.
- Microfarad Values: Two values indicated (e.g., 5 µF for fan motor, 40 µF for compressor).
- Voltage Rating: Should be equal to or greater than the original capacitor.
Replacing Run Capacitors
- Microfarad Rating: Match the exact rating, or within 10% deviation.
- Voltage Rating: Equal to or greater than the original capacitor's rating.
Summary of Run Capacitor Operation
- Starting and Running:
- Contactors apply line power through the run capacitor to start winding.
- Limits current, promotes phase shift, improves efficiency, and provides some starting torque.