Temperature Difference (TD) vs. Delta T:
- Temperature Difference (TD): The difference between the air temperature entering the evaporator and the refrigerant boiling temperature inside the evaporator.
- Usage: Mostly in commercial refrigeration applications.
- Delta T: The difference between the air temperature entering the evaporator and the air temperature leaving the evaporator.
- Usage: Mostly in air conditioning applications.
Examples:
- Air Conditioning Evaporator:
- TD Example: 75°F return air, 40°F refrigerant boiling temperature = 35°F TD.
- Delta T Example: 75°F air entering, 55°F air leaving = 20°F Delta T.
Measuring TD and Delta T:
- Evaporator TD Measurement:
- Measure suction pressure (e.g., 72 psig).
- Convert to evaporating temperature using a pressure-temperature chart (e.g., 42°F).
- Subtract the evaporating temperature from the return air temperature (e.g., 75°F - 42°F = 33°F TD).
- Delta T Measurement:
- Drill small holes in the supply and return boxes.
- Insert temperature probes and allow the unit to run.
- Measure air temperature in return and supply (e.g., 75°F return air, 56°F supply air = 19°F Delta T).
Superheat:
- Definition: The measurable heat above the saturation temperature or the amount of sensible heat added to the vapor after evaporation.
- Importance: Verifies full evaporation, preventing floodback or liquid flooding that could damage the compressor.
- Superheat Locations:
- Evaporator Superheat: Measured at the evaporator outlet.
- Compressor (Total) Superheat: Measured at the compressor inlet.
Superheat Calculation Example:
Evaporator Superheat:
- Measure low-side pressure (e.g., 69 psig for R-22).
- Convert to evaporating temperature (e.g., 40°F).
- Place a thermometer on the suction line at the evaporator outlet (e.g., 50°F).
- Subtract the evaporating temperature from the suction line temperature (e.g., 50°F - 40°F = 10°F evaporator superheat).
Compressor Superheat:
- Measure temperature at the compressor inlet (e.g., 60°F).
- Total superheat is the difference between the evaporating temperature and compressor inlet temperature (e.g., 60°F - 40°F = 20°F compressor superheat).
Superheat Guidelines:
- Rule of Thumb: Average evaporator superheat is 10°F, with a range of 5-20°F depending on the application.
- High Superheat (Above 20°F): Indicates the evaporator is starving for refrigerant (boiling off too soon).
- Low Superheat: Indicates the evaporator is flooding, risking liquid refrigerant entering the suction line and damaging the compressor.
No comments:
Post a Comment