1. Solenoid Valve:
- Controls the flow of refrigerant and has various applications in refrigeration systems.
- Automatic Pump Down Solenoid:
- Placed in the liquid line.
- Closes to stop refrigerant flow when desired temperature is met.
- Compressor pumps refrigerant to the high side, reducing pressure and cycling the compressor off to prevent refrigerant migration and flooded starts.
- Hot Gas or Discharge Bypass Valve:
- Bypasses hot gas into the evaporator or discharge gas to the suction line.
- Maintains minimum pressure and temperature in the evaporator and prevents excessive compression ratios and overheating.
- Requires a desuperheating thermostatic expansion valve for temperature control.
- Solenoid valves can be normally open or closed and are operated by a controller or manually if needed.
2. Filter Dryers:
- Absorb moisture and filter debris from the system.
- Liquid Line Filter Dryers:
- Installed between the condenser outlet and the metering device.
- Two types: Spun copper dryers with loose desiccant beads and solid core molecular sieve dryers with steel housing.
- Solid core dryers start with lower moisture content, extending their lifespan and reducing maintenance costs.
3. Sight Glass:
- Allows technicians to verify that a solid column of liquid refrigerant is available to the metering device.
- Some sight glasses have a moisture indicator.
- Installed after the filter dryer to check for bubbles, indicating potential restrictions.
4. Accumulator:
- Prevents liquid refrigerant from reaching the compressor.
- Installed in the suction line to allow liquid to boil off and return as vapor.
- Should never be insulated; requires ambient heat to vaporize liquid refrigerant.
5. Oil Separator:
- Installed in the discharge line to remove entrained oil from the refrigerant and return it to the compressor crankcase.
- Beneficial for systems where oil return from the evaporator is difficult, especially in low-temperature applications.
- Major issue is debris in the float valve; can overfill the compressor with oil if stuck open.
- An oil filter can prevent this problem.
6. Refrigerants:
- Rated by ozone depletion level and global warming potential.
- High numbers indicate worse environmental impact.
- Regulatory bodies phase out refrigerants with high environmental impact and mandate more eco-friendly alternatives.
- Examples of alternatives: Propane (R290), carbon dioxide, and ammonia.
- Regulations:
- Vary by country. For example, the US EPA restricts R404a due to high global warming potential.
- The EPA's SNAP program lists several alternatives.