Diagnosing A/C Systems : Inadequate Evaporator Airflow

 Overview:

  • Inadequate airflow across the evaporator coil can be caused by a dirty or iced evaporator, a clogged air filter, an obstructed return register, or a dirty blower wheel. This issue affects the system’s ability to absorb heat, leading to various symptoms.

Effects of Inadequate Airflow in Systems with a Fixed Bore Metering Device:

  1. Evaporator Temperature:

    • Condition: Decreases.
    • Reason: Reduced airflow leads to less heat being absorbed, lowering the pressure and temperature in the evaporator.
  2. Superheat:

    • Condition: Decreases, potentially to zero.
    • Reason: With less heat absorbed, the refrigerant may not fully vaporize, causing liquid refrigerant to exit the evaporator and potentially flood back to the compressor.
  3. Condensing Temperature:

    • Condition: Decreases.
    • Reason: Less heat is transferred to the refrigerant, leading to lower high side pressure and condensing temperature.
  4. Subcooling:

    • Condition: Remains relatively normal.
    • Reason: The amount of refrigerant in the condenser remains adequate, so subcooling does not significantly change.

Example: Dirty or Iced Evaporator on a 10-SEER Air Conditioning System with R22 (Fixed Bore Metering Device):

  • Normal Operating Conditions:

    • Low side pressure: 69 PSIG → 40°F evaporating temperature.
    • High side pressure: 278 PSIG → 125°F condensing temperature.
    • Ambient air: 95°F, resulting in a 30°F condenser split.
    • Subcooling: Approximately 10°F.
  • Inadequate Airflow Conditions:

    • Evaporator Side:

      • Low side pressure decreases to 43 PSIG → 20°F evaporating temperature.
      • Evaporator temperature difference (TD) increases to 60°F (80°F return air - 20°F evaporator temperature).
      • Superheat decreases to 0°F, indicating liquid refrigerant leaving the evaporator and entering the suction line, potentially causing compressor damage.
    • Condensing Side:

      • High side pressure decreases to 242 PSIG → 115°F condensing temperature.
      • Condenser split decreases to 20°F (115°F condensing temperature - 95°F ambient air).
      • Subcooling remains relatively normal at around 10°F.

Effects of Inadequate Airflow in Systems with a Thermostatic Expansion Valve (TEV):

  1. Evaporator Temperature:

    • Condition: Decreases.
    • Reason: Similar to fixed bore systems, reduced airflow lowers the heat absorbed, decreasing evaporator temperature.
  2. Superheat:

    • Condition: Remains normal.
    • Reason: The TEV adjusts refrigerant flow to maintain consistent superheat, even when airflow is reduced.
  3. Condensing Temperature:

    • Condition: Decreases.
    • Reason: Less heat is absorbed in the evaporator, leading to lower condensing temperature and pressure.
  4. Subcooling:

    • Condition: Remains relatively normal.
    • Reason: The refrigerant in the condenser remains adequate, so subcooling does not significantly change.

Example: Dirty or Iced Evaporator on a 10-SEER Air Conditioning System with R22 (TEV System):

  • Normal Operating Conditions:

    • Low side pressure: 69 PSIG → 40°F evaporating temperature.
    • High side pressure: 278 PSIG → 125°F condensing temperature.
    • Ambient air: 95°F, resulting in a 30°F condenser split.
    • Subcooling: Approximately 10°F.
  • Inadequate Airflow Conditions:

    • Evaporator Side:

      • Low side pressure decreases to 43 PSIG → 20°F evaporating temperature.
      • Evaporator temperature difference (TD) increases to 60°F (80°F return air - 20°F evaporator temperature).
      • Superheat remains normal at 10°F, thanks to the TEV’s ability to modulate refrigerant flow.
    • Condensing Side:

      • High side pressure decreases to 242 PSIG → 115°F condensing temperature.
      • Condenser split decreases to 20°F.
      • Subcooling remains normal at around 10°F.

Key Takeaways:

  • Low Evaporator Temperature and Superheat: Indicators of inadequate airflow, causing the evaporator to ice over or starve.
  • Low Condensing Temperature: Results from reduced heat absorption, leading to lower high side pressure.
  • Subcooling: Remains relatively unaffected, making it less useful for diagnosing airflow issues.
  • TEV Systems: Maintain normal superheat even under reduced airflow, but other symptoms like low evaporator temperature and condensing temperature still apply.

Action Steps:

  • Check for Airflow Obstructions: Start by inspecting and cleaning the air filter, checking for any obstructions in return registers, and ensuring the blower wheel is clean.
  • Monitor for Ice: If the evaporator coil is iced over, allow it to thaw and check for underlying airflow issues before restarting the system.

No comments:

Post a Comment

Mechanics Introduction

  산업 역학에서 작업(work), 에너지(energy), 힘(force), 그리고 동력(power) 간의 관계를 이해하는 것은 작업의 효율성을 극대화하는 데 필수적입니다. 역학은 에너지, 힘, 그리고 동력이 함께 작용하여 작업을 수행하는 방식을 연구...