Overview:
- Inadequate airflow across the evaporator coil can be caused by a dirty or iced evaporator, a clogged air filter, an obstructed return register, or a dirty blower wheel. This issue affects the system’s ability to absorb heat, leading to various symptoms.
Effects of Inadequate Airflow in Systems with a Fixed Bore Metering Device:
Evaporator Temperature:
- Condition: Decreases.
- Reason: Reduced airflow leads to less heat being absorbed, lowering the pressure and temperature in the evaporator.
Superheat:
- Condition: Decreases, potentially to zero.
- Reason: With less heat absorbed, the refrigerant may not fully vaporize, causing liquid refrigerant to exit the evaporator and potentially flood back to the compressor.
Condensing Temperature:
- Condition: Decreases.
- Reason: Less heat is transferred to the refrigerant, leading to lower high side pressure and condensing temperature.
Subcooling:
- Condition: Remains relatively normal.
- Reason: The amount of refrigerant in the condenser remains adequate, so subcooling does not significantly change.
Example: Dirty or Iced Evaporator on a 10-SEER Air Conditioning System with R22 (Fixed Bore Metering Device):
Normal Operating Conditions:
- Low side pressure: 69 PSIG → 40°F evaporating temperature.
- High side pressure: 278 PSIG → 125°F condensing temperature.
- Ambient air: 95°F, resulting in a 30°F condenser split.
- Subcooling: Approximately 10°F.
Inadequate Airflow Conditions:
Evaporator Side:
- Low side pressure decreases to 43 PSIG → 20°F evaporating temperature.
- Evaporator temperature difference (TD) increases to 60°F (80°F return air - 20°F evaporator temperature).
- Superheat decreases to 0°F, indicating liquid refrigerant leaving the evaporator and entering the suction line, potentially causing compressor damage.
Condensing Side:
- High side pressure decreases to 242 PSIG → 115°F condensing temperature.
- Condenser split decreases to 20°F (115°F condensing temperature - 95°F ambient air).
- Subcooling remains relatively normal at around 10°F.
Effects of Inadequate Airflow in Systems with a Thermostatic Expansion Valve (TEV):
Evaporator Temperature:
- Condition: Decreases.
- Reason: Similar to fixed bore systems, reduced airflow lowers the heat absorbed, decreasing evaporator temperature.
Superheat:
- Condition: Remains normal.
- Reason: The TEV adjusts refrigerant flow to maintain consistent superheat, even when airflow is reduced.
Condensing Temperature:
- Condition: Decreases.
- Reason: Less heat is absorbed in the evaporator, leading to lower condensing temperature and pressure.
Subcooling:
- Condition: Remains relatively normal.
- Reason: The refrigerant in the condenser remains adequate, so subcooling does not significantly change.
Example: Dirty or Iced Evaporator on a 10-SEER Air Conditioning System with R22 (TEV System):
Normal Operating Conditions:
- Low side pressure: 69 PSIG → 40°F evaporating temperature.
- High side pressure: 278 PSIG → 125°F condensing temperature.
- Ambient air: 95°F, resulting in a 30°F condenser split.
- Subcooling: Approximately 10°F.
Inadequate Airflow Conditions:
Evaporator Side:
- Low side pressure decreases to 43 PSIG → 20°F evaporating temperature.
- Evaporator temperature difference (TD) increases to 60°F (80°F return air - 20°F evaporator temperature).
- Superheat remains normal at 10°F, thanks to the TEV’s ability to modulate refrigerant flow.
Condensing Side:
- High side pressure decreases to 242 PSIG → 115°F condensing temperature.
- Condenser split decreases to 20°F.
- Subcooling remains normal at around 10°F.
Key Takeaways:
- Low Evaporator Temperature and Superheat: Indicators of inadequate airflow, causing the evaporator to ice over or starve.
- Low Condensing Temperature: Results from reduced heat absorption, leading to lower high side pressure.
- Subcooling: Remains relatively unaffected, making it less useful for diagnosing airflow issues.
- TEV Systems: Maintain normal superheat even under reduced airflow, but other symptoms like low evaporator temperature and condensing temperature still apply.
Action Steps:
- Check for Airflow Obstructions: Start by inspecting and cleaning the air filter, checking for any obstructions in return registers, and ensuring the blower wheel is clean.
- Monitor for Ice: If the evaporator coil is iced over, allow it to thaw and check for underlying airflow issues before restarting the system.
No comments:
Post a Comment