Diagnosing A/C Systems : Temperature Split and Evaporator TD

 Understanding SEER Ratings and System Performance:

  • 10 SEER Unit:

    • Condenser Split: 30° ± 5°
    • Example: 95°F ambient air, 125°F condensing temperature, resulting in a 30° split.
    • Subcooling: 10°F (125°F condensing temperature - 115°F liquid line temperature).
    • Evaporator Temperature Difference (TD): 35°F (75°F return air - 40°F evaporator temperature).
    • Superheat: 10°F (50°F suction line temperature - 40°F evaporator temperature).
  • 12 SEER Unit:

    • Condenser Split: Decreases with higher SEER.
    • Example: 95°F ambient air, 120°F condensing temperature, 30°F split.
    • Subcooling: Remains at 10°F (120°F condensing temperature - 110°F liquid line temperature).
    • Evaporator TD: 35°F, with consistent superheat due to the thermostatic expansion valve.
  • 13 SEER Unit (New Minimum):

    • Condenser Split: 20° (95°F ambient air, 115°F condensing temperature).
    • Subcooling: 10°F, consistent with previous units.
  • 14 SEER Unit:

    • Condenser Split: 15° (95°F ambient air, 110°F condensing temperature).
    • Subcooling: Remains at 10°F, but high side pressure and power consumption are reduced.

General Troubleshooting Procedures:

  1. Ensure Proper Airflow:

    • Check the filter; clean if necessary.
    • Average airflow should be about 400 CFM per ton of capacity.
  2. Determine Normal Operating Conditions:

    • Establish normal evaporator temperature, superheat, condensing temperature, and subcooling.
  3. Assess System Conditions:

    • Evaluate if each condition is normal, higher than normal, or lower than normal.

Evaporator Temperature Difference (TD) Analysis:

  • Normal Evaporator TD: 30° to 40° below return air temperature.

    • Example: 75°F return air results in 35°F to 45°F evaporator temperature.
  • High Evaporator Temperature:

    • Indicates high pressure, possibly due to a flooded evaporator or excessive heat load.
  • Low Evaporator Temperature:

    • Indicates starving of refrigerant or low heat load.
  • Effect of Evaporator TD on Temperature:

    • Higher evaporator temperature: TD below 30°F.
    • Lower evaporator temperature: TD above 40°F.
    • Keep evaporating temperature above freezing (32°F) to avoid issues since air conditioning systems lack automatic defrost mechanisms.

No comments:

Post a Comment

Mechanics Introduction

  산업 역학에서 작업(work), 에너지(energy), 힘(force), 그리고 동력(power) 간의 관계를 이해하는 것은 작업의 효율성을 극대화하는 데 필수적입니다. 역학은 에너지, 힘, 그리고 동력이 함께 작용하여 작업을 수행하는 방식을 연구...