Introduction to Voltage Tolerances
- Motors typically operate within ±10% of the rated voltage.
- Example: A 240V motor can safely operate between 216V and 264V.
- Motors with extended voltage ratings (e.g., 208V/230V) have a 5% tolerance below and 10% above the rated voltage.
- Below minimum voltage (e.g., 197V for a 208V motor) can cause starting issues.
Voltage Imbalance in Three Phase Motors
- Voltage imbalance refers to the difference in voltage between the three phases.
- Maximum allowable voltage imbalance is 2%.
- A 3% voltage imbalance can result in a 30% current imbalance, leading to motor heat, overload trips, or winding damage.
Measuring Voltage Imbalance
- Measure voltages at the load side of the contactor (T1, T2, T3).
- Example: Measure 209V (T1 to T2), 211V (T1 to T3), and 214V (T2 to T3).
- Calculate the average voltage and find the maximum deviation.
- Example: Average voltage = 211.3V, maximum deviation = 2.7V.
- Voltage imbalance = (2.7V ÷ 211.3V) × 100 = 1.3% (safe as it’s within 2%).
Handling High Voltage Imbalance
- Check line side voltage if a high imbalance is detected at the load side.
- A high imbalance may result from loose connections or pitted contacts.
- Consider contacting the utility company or building electrician if the problem persists.
Optional Control Component: Phase Voltage Monitor
- Monitors both line side and load side voltage.
- Detects issues like pitted contacts and voltage imbalances.
- Can protect the motor by disconnecting power if an imbalance or voltage issue is detected.