Safety Preparation:
Only certified technicians with appropriate expertise should perform work involving refrigerants.
Create a detailed work plan and review the refrigerant’s safety data sheet.
Ensure a Class B fire extinguisher is nearby.
Avoid overheating refrigerant cylinders (keep below 125°F/52°C) and avoid direct sunlight.
Set up safety barriers and signage; keep ignition sources away from the work area.
Recommended work zone radius: 10 feet around equipment.
Lockout/Tagout and Ventilation:
Use lockout/tagout procedures for equipment.
Shut down adjacent equipment that may have ignition sources or hot surfaces.
Ensure proper ventilation and use refrigerant detectors to check for toxic or flammable atmospheres.
Never tamper with customer refrigerant detection systems.
Handling Cylinders:
Store cylinders upright at all times to prevent a high concentration of liquid refrigerant release.
Ensure adequate ventilation during work to disperse released refrigerant, as A2L refrigerants (e.g., R-1234ZE, R-454B) are heavier than air and can accumulate on the ground.
Working with Electrical Components:
Discharge capacitors safely using proper tools (avoid screwdrivers to prevent sparks).
Ensure no exposed live electrical components.
Verify continuity of the ground wire during electrical work.
Final Safety Steps:
Follow manufacturer’s maintenance and service guidelines.
Avoid confined spaces and ensure ventilation during soldering or brazing to prevent toxic gas formation in case of a refrigerant leak.
Safe Work Zone:
Establish a safe work zone before refrigerant handling.
Remove refrigerants according to local and national regulations.
Purge the circuit with inert gas (optional step) and evacuate the system before brazing or cutting parts.
Brazing and Leak Testing:
Purge brazing points with nitrogen during the repair process.
Perform a leak test before recharging with refrigerant.
Purging and Charging:
Purge flammable refrigerants with oxygen-free nitrogen, vent the system to the atmosphere, and repeat until no refrigerant remains.
Use only the correct recovery cylinders, and ensure hoses and lines are short to minimize refrigerant content.
Pressure test the system with purging gas before recharging and ensure the correct amount of refrigerant is added, as indicated on the system's data plate.
Recovery Procedures:
Use designated recovery cylinders equipped with pressure relief valves and ensure they are labeled for the correct refrigerant.
Empty recovery cylinders should be evacuated and cooled before use.
Check that recovery equipment is suitable for flammable refrigerants and in good working order.
Always have calibrated weighing scales and leak-proof hoses for safe refrigerant recovery.
Transportation Guidelines:
The Department of Transportation (DOT) regulates weight limits:
Max weight per cylinder: 220 lbs; max weight in a service vehicle: 440 lbs.
Max weight for pickup or stake bed trucks: 1,000 lbs.
Some A2L refrigerants can be transported horizontally if the pressure relief valve is in the 12 o’clock position (manufacturer-specific).
Cylinders should be stored in vented cabinets during transport and positioned per manufacturer’s instructions.
Storage Requirements:
Refrigerant cylinders should be stored in cool, dry areas, away from direct sunlight and heat sources.
Maximum allowable quantities (MAQ) for refrigerant storage depend on facility classification (e.g., mercantile, storage warehouse, factory):
With sprinkler systems: 40,000 lbs for mercantile/storage, 20,000 lbs for factories.
Without sprinklers: 20,000 lbs for mercantile/storage, 10,000 lbs for factories.
Storage areas must be ventilated, free of combustibles, ignition sources, and equipped with clear safety signs and fire safety measures.
Mechanical Room Guidelines:
Mechanical rooms must comply with local regulations and conduct risk assessments.
Equipment exceeding 80% of the refrigerant’s auto-ignition temperature should be placed in separate rooms.
Auto-ignition temperatures:
R-1234ZE: 694°F (367.8°C)
R-454B: 928.4°F (498°C)
R-32: 1198.4°F (648°C)
Electrical components (ventilation, pumps, detectors) must be designed for explosive atmospheres.
Machine rooms should not be occupied or used for storage and must prevent refrigerant from entering adjacent areas.