EPA 608 Type III

 Certification Requirements

  • Technicians handling low-pressure appliances (such as chillers) must be Type III certified or hold Universal certification.

  • Low-pressure systems operate under a vacuum, increasing the risk of air and moisture infiltration.

Leak Detection for Low-Pressure Systems

  • Purge Units: Essential for removing non-condensables that leak into the system, often indicated by high head pressure or frequent purge operation.

  • Hydrostatic Tube Testing: Used to test for leaks; a maximum test pressure of 10 psig is applied.

  • Moisture Prevention: Moisture commonly enters low-pressure systems through gaskets or fittings; leak detection should be frequent.

  • Air Accumulation Prevention: Maintain slightly positive pressure during system downtime to avoid air entry.

Leak Repair Requirements

  • Leak Thresholds:

    • Comfort Cooling: 10% per year.

    • Commercial Refrigeration: 20% per year.

    • Industrial Process Refrigeration (IPR): 30% per year.

  • Repair or Retirement: If leak thresholds exceed these values, repairs, retrofitting, or retirement of the appliance are mandatory.

Repair Deadlines

  • 30 Days: For appliances exceeding the threshold leak rate, repairs must reduce leaks below the threshold within 30 days.

  • 18 Months: If the leak rate exceeds 50 pounds, 18 months is allowed to retrofit or retire the appliance if using a refrigerant exempt from venting prohibition.

System Mothballing

  • Does not require removal of the appliance. If refrigerant is recovered, storing the appliance at atmospheric pressure can extend deadlines.

Recovery Techniques for Low-Pressure Systems

  • High-Pressure Cut-Out: The cut-out level for low-pressure recovery units is set at 10 psig.

  • Recovery Process:

    • Begin with liquid refrigerant removal followed by vapor recovery.

    • Large systems like 350-ton R-123 chillers may retain about 100 pounds of refrigerant in the vapor state at 0 psig.

  • Dehydration with Nitrogen: For moisture-heavy systems, use nitrogen to prevent water from freezing during evacuation.

Recovery Equipment and Requirements

  • Water-Cooled Recovery: Recommended for faster recovery and to prevent freezing.

  • Oil Heating: Before replacing refrigerant oil, heat to 130°F to release refrigerant trapped in oil.

  • Evacuation Levels: Recover refrigerants to an absolute pressure of 25 mm Hg. Disposal of low-pressure appliances requires records for three years.

Recharging Techniques

  • Oil Sampling: Before recharging, take an oil sample if the unit has had a compressor burn-out.

  • Prevent Freezing: For systems charged in a vacuum, avoid freezing by referencing the pressure-temperature (P-T) chart.

  • Pressure Adjustments: Charge refrigerant vapor into the system to avoid freezing; liquid refrigerant is added through the evaporator charging valve.

Safety Protocols

  • TLV-TWA Standard: When exposure limits are exceeded, ASHRAE Standard 15-2013 mandates alarms and mechanical ventilation.

  • Room Sensors: Required to detect refrigerant leaks for all safety groups due to the asphyxiation risk of refrigerants.

  • Pressure Relief Valve: Relief valves must be vented outdoors and installed in parallel, not in series.

  • Protective Equipment: Technicians should wear gloves and safety goggles when handling liquid refrigerants.

General Handling and Precautions

  • Rupture Discs: Located on evaporators, rupture at 15 psig to release pressure.

  • Refrigerant Charging: Avoid over-pressurizing the system when charging through the evaporator.

  • Sight Glass Maintenance: Use isopropyl alcohol to remove ice from sight glasses and other components.


No comments:

Post a Comment

Mechanics Introduction

  산업 역학에서 작업(work), 에너지(energy), 힘(force), 그리고 동력(power) 간의 관계를 이해하는 것은 작업의 효율성을 극대화하는 데 필수적입니다. 역학은 에너지, 힘, 그리고 동력이 함께 작용하여 작업을 수행하는 방식을 연구...