Overview:
- Diagnosing an air conditioning system with a refrigerant leak or undercharge can be challenging, especially when the symptoms are subtle. Systems may run but fail to provide adequate cooling, particularly in hotter conditions.
Common Symptoms of Undercharge:
Evaporator Temperature and Low Side Pressure:
- Condition: Both will be lower than normal.
- Reason: Lack of refrigerant leads to lower pressure and temperature in the evaporator.
Superheat:
- Condition: Superheat will be higher than normal.
- Reason: With less refrigerant, it boils off quickly, causing superheating to start earlier in the coil.
Condensing Temperature:
- Condition: Lower than normal.
- Reason: Reduced heat absorption in the evaporator leads to lower condensing pressure and temperature.
Subcooling:
- Condition: Subcooling will be low or nonexistent.
- Reason: Insufficient refrigerant means there’s not enough liquid to cool below the condensing temperature, sometimes resulting in vapor entering the liquid line.
Example of a 10-SEER System with a Low Charge:
Normal Operating Conditions:
- Low side pressure: 69 PSIG → 40°F evaporator temperature.
- High side pressure: 278 PSIG → 125°F condensing temperature.
- Ambient air: 95°F, resulting in a 30°F condenser split.
- Subcooling: Typically around 10-15°F.
Symptoms of Low Charge:
- High side pressure drops to 211 PSIG → 105°F condensing temperature.
- Condenser split: 10°F (105°F condensing temperature - 95°F ambient air), significantly lower than the normal 30°F.
- Subcooling: None, indicating the presence of vapor in the liquid line, which may cause bubbles in the sight glass.
- Low side pressure: Drops to 43 PSIG → 20°F evaporator temperature.
- High evaporator temperature difference (TD): 60°F (80°F return air - 20°F evaporator temperature).
- Superheat: 50°F, measured as 70°F on the suction line at the evaporator outlet, indicating significant superheating.
Key Takeaways:
- High Superheat and Low Subcooling: Indicators of a refrigerant undercharge or leak.
- Low Condensing Temperature and Pressure: Due to insufficient refrigerant to absorb and reject heat effectively.
- Evaporator Temperature Difference: High TD is a result of the evaporator struggling to cool with low refrigerant levels.