Diagnosing A/C Systems : Refrigerant Overcharge

 Overview:

  • Overcharging a refrigerant system leads to increased pressure and temperature, which can negatively impact system performance. The effects vary depending on whether the system uses a fixed bore metering device or a thermostatic expansion valve (TEV).

Effects of Refrigerant Overcharge in Systems with a Fixed Bore Metering Device:

  1. Condensing Temperature:

    • Condition: Increases above normal.
    • Reason: Excess refrigerant takes up space in the condenser, raising pressure and condensing temperature.
  2. Subcooling:

    • Condition: Increases above normal.
    • Reason: More liquid refrigerant is available for sensible cooling, increasing subcooling.
  3. Evaporator Temperature:

    • Condition: Increases.
    • Reason: Higher liquid line pressure forces more refrigerant into the evaporator, raising evaporating temperature.
  4. Superheat:

    • Condition: Decreases, possibly no superheat at all.
    • Reason: Excess refrigerant causes flooding in the evaporator, leading to little or no superheating of the refrigerant.

Example: Overcharge on a 10-SEER Air Conditioning System with R22 (Fixed Bore Metering Device):

  • Normal Operating Conditions:

    • Low side pressure: 69 PSIG → 40°F evaporating temperature.
    • High side pressure: 278 PSIG → 125°F condensing temperature.
    • Ambient air: 95°F, resulting in a 30°F condenser split.
    • Subcooling: Approximately 10°F.
  • Overcharge Conditions:

    • High side pressure increases to 360 PSIG → 145°F condensing temperature.
    • Condenser split increases to 50°F (145°F condensing temperature - 95°F ambient air).
    • Subcooling increases to 25°F (145°F condensing temperature - 120°F liquid line temperature).
    • Low side pressure increases to 102 PSIG → 60°F evaporating temperature.
    • Evaporator temperature difference (TD) decreases to 20°F (80°F return air - 60°F evaporator temperature).
    • Superheat drops to 0°F, indicating liquid refrigerant entering the suction line and potential compressor damage.

Effects of Refrigerant Overcharge in Systems with a Thermostatic Expansion Valve (TEV):

  1. Condensing Temperature:

    • Condition: Increases.
    • Reason: Excess refrigerant takes up space in the condenser, raising pressure and condensing temperature.
  2. Subcooling:

    • Condition: Increases.
    • Reason: TEV backs up refrigerant in the condenser, allowing more liquid to subcool.
  3. Evaporator Temperature:

    • Condition: Remains normal.
    • Reason: TEV regulates the amount of refrigerant entering the evaporator, maintaining a consistent evaporating temperature.
  4. Superheat:

    • Condition: Remains normal.
    • Reason: TEV maintains superheat by modulating refrigerant flow based on the evaporator load.

Example: Overcharge on a 10-SEER Air Conditioning System with R22 (TEV):

  • High side pressure increases to 360 PSIG → 145°F condensing temperature.
  • Condenser split increases to 50°F (145°F condensing temperature - 95°F ambient air).
  • Subcooling increases to 25°F.
  • Low side pressure remains relatively normal at 76 PSIG → 45°F evaporating temperature.
  • Evaporator TD remains normal at 35°F (80°F return air - 45°F evaporator temperature).
  • Superheat remains normal at 10°F (55°F suction line temperature - 45°F evaporating temperature).

Key Takeaways:

  • Increased Condensing Temperature and Subcooling: Common indicators of refrigerant overcharge.
  • Fixed Bore Metering Device: Overcharge causes high evaporator temperatures and low or zero superheat, risking compressor damage.
  • TEV Systems: Although the evaporator side may operate normally, overcharge still results in higher compressor amp draw and reduced system efficiency due to increased high side pressure.

No comments:

Post a Comment

Mechanics Introduction

  산업 역학에서 작업(work), 에너지(energy), 힘(force), 그리고 동력(power) 간의 관계를 이해하는 것은 작업의 효율성을 극대화하는 데 필수적입니다. 역학은 에너지, 힘, 그리고 동력이 함께 작용하여 작업을 수행하는 방식을 연구...