Overview:
- Overcharging a refrigerant system leads to increased pressure and temperature, which can negatively impact system performance. The effects vary depending on whether the system uses a fixed bore metering device or a thermostatic expansion valve (TEV).
Effects of Refrigerant Overcharge in Systems with a Fixed Bore Metering Device:
Condensing Temperature:
- Condition: Increases above normal.
- Reason: Excess refrigerant takes up space in the condenser, raising pressure and condensing temperature.
Subcooling:
- Condition: Increases above normal.
- Reason: More liquid refrigerant is available for sensible cooling, increasing subcooling.
Evaporator Temperature:
- Condition: Increases.
- Reason: Higher liquid line pressure forces more refrigerant into the evaporator, raising evaporating temperature.
Superheat:
- Condition: Decreases, possibly no superheat at all.
- Reason: Excess refrigerant causes flooding in the evaporator, leading to little or no superheating of the refrigerant.
Example: Overcharge on a 10-SEER Air Conditioning System with R22 (Fixed Bore Metering Device):
Normal Operating Conditions:
- Low side pressure: 69 PSIG → 40°F evaporating temperature.
- High side pressure: 278 PSIG → 125°F condensing temperature.
- Ambient air: 95°F, resulting in a 30°F condenser split.
- Subcooling: Approximately 10°F.
Overcharge Conditions:
- High side pressure increases to 360 PSIG → 145°F condensing temperature.
- Condenser split increases to 50°F (145°F condensing temperature - 95°F ambient air).
- Subcooling increases to 25°F (145°F condensing temperature - 120°F liquid line temperature).
- Low side pressure increases to 102 PSIG → 60°F evaporating temperature.
- Evaporator temperature difference (TD) decreases to 20°F (80°F return air - 60°F evaporator temperature).
- Superheat drops to 0°F, indicating liquid refrigerant entering the suction line and potential compressor damage.
Effects of Refrigerant Overcharge in Systems with a Thermostatic Expansion Valve (TEV):
Condensing Temperature:
- Condition: Increases.
- Reason: Excess refrigerant takes up space in the condenser, raising pressure and condensing temperature.
Subcooling:
- Condition: Increases.
- Reason: TEV backs up refrigerant in the condenser, allowing more liquid to subcool.
Evaporator Temperature:
- Condition: Remains normal.
- Reason: TEV regulates the amount of refrigerant entering the evaporator, maintaining a consistent evaporating temperature.
Superheat:
- Condition: Remains normal.
- Reason: TEV maintains superheat by modulating refrigerant flow based on the evaporator load.
Example: Overcharge on a 10-SEER Air Conditioning System with R22 (TEV):
- High side pressure increases to 360 PSIG → 145°F condensing temperature.
- Condenser split increases to 50°F (145°F condensing temperature - 95°F ambient air).
- Subcooling increases to 25°F.
- Low side pressure remains relatively normal at 76 PSIG → 45°F evaporating temperature.
- Evaporator TD remains normal at 35°F (80°F return air - 45°F evaporator temperature).
- Superheat remains normal at 10°F (55°F suction line temperature - 45°F evaporating temperature).
Key Takeaways:
- Increased Condensing Temperature and Subcooling: Common indicators of refrigerant overcharge.
- Fixed Bore Metering Device: Overcharge causes high evaporator temperatures and low or zero superheat, risking compressor damage.
- TEV Systems: Although the evaporator side may operate normally, overcharge still results in higher compressor amp draw and reduced system efficiency due to increased high side pressure.
No comments:
Post a Comment